Modular Conceptpower 120 UPS Featured

171221-161837

Designed for small to medium-sized data centers, Conceptpower 120 fulfills power requirements from 20 kW to 600 kW and provides maximum flexibility, redundancy and reliability to protect critical 

Today’s data centers require continuous uptime. That target is why ABB’s Conceptpower DPA 120 is based on Decentralized Parallel Architecture (DPA). Only a truly redundant architecture like DPA allows online modules to be swapped out while the system is running. Each high-reliability, standardized module is self-contained and can be swapped at any time, so nothing has to be ever switched off – making routine maintenance safe and easy.

Conceptpower DPA 120 is designed to secure continuity of critical operations for small to mid-sized data centers, server rooms and other IT applications. It also protects industrial automation processes, healthcare facilities and many other vertical markets where operations are of a critical nature.

 

171221-161837

171221-161844

171221-161852

171221-161904

171221-161914

 

Features

BASIC SYSTEM CONFIGURATION THE MODULE INCLUDES:

  • 20kW
  • True Online Double Conversion UPS
  • Built-In Modular Isolation
  • Built-In Backfeed Protection
  • Individual Module Display
  • HMI Interface With Mimic Diagram And LCD Providing Information In Five Languages

THE FRAME INCLUDES:

  • 120kW Rated Power In Single Frame
  • Bottom Cable Entry (Standard)
  • Rectifier, Bypass Terminals (Single Or Dual-Input Mains Connection Available) And UPS Output Terminals
  • Battery Breakers And Output Switches For Each Module Set
  • Graphical Color Touch Screen System Display
  • Communication Interfaces: RS-232 And USB Ports, I/O Dry Contacts (E.G. EPO, GEN On) And External Bypass Interlock

OPTIONS

  • Battery Monitoring
  • Seismic Bracing
  • Maintenance Bypass Cabinet
  • Control And Monitoring (Modbus RS-485, Modbus TCP/IP, SNMP, Bacnet And Others)
  • Line-And-Match Battery Cabinets

 

Specifications

GENERAL DATA CONCEPTPOWER DPA 120 UL UPS

  • System Power Range 20kW–600kW
  • Nominal Power/Module 20kW
  • Nominal Power/Frame (Capacity) 600kW
  • Output Power Factor 1.0
  • Topology Double Conversion, Transformerless, Modular, Decentralized Parallel Architecture
  • Parallel Configuration Up To 6 Modules In One Frame / Up To 5 Frames In Parallel
  • Cable Entry Bottom
  • Serviceability Front Access Only
  • Back-Feed Protection Built-In (Standard)
  • Connection 5-Wires, 3-Phase + Neutral + Ground

INPUT

  • Nominal Input Voltage 3 X 208/120V + Neutral + Ground
  • Voltage Tolerance < 100% (–15%, +10%), < 80% (–20%, +10%), < 60% (–30%, +10%)
  • Input Distortion THDi < 4% At 100% Load
  • Frequency Range 50/60Hz ± 5%
  • Power Factor 0.99 @ 100% Load
  • Walk In/Soft Start Yes

OUTPUT

  • Rated Output Voltage 3 X 208/120V + Neutral + Ground
  • Voltage Tolerance ± 2.5%
  • Voltage Distortion THDv < 2% In Linear Mode
  • Frequency 50/60Hz

EFFICIENCY

  • AC-AC Up To 94% At Nominal Load

ENVIRONMENT

  • Protection Rating IP 20
  • Storage Temperature −25° To +70°C
  • Operating Temperature 0° To +40°C
  • Altitude (Above Sea Level) 1000 M Without De-Rating

BATTERIES

  • Number Of 12V Jars/String 25 – 35 Jars
  • Types VRLA, NiCd
  • Battery Charger Decentralized Charger In Each Module Set

COMMUNICATIONS

  • User Interface Graphical Touch Screen (One Per Frame As Standard) Decentralized LCD + Mimic Diagram (One Per Module As Standard)
  • Communication Ports USB, RS-232, Voltage-Free Contacts, SNMP (Optional)
  • Customer Interface Remote Shutdown, Gen-Set Interface, External Bypass Contact

COMPLIANCY

  • Safety UL 1778 5th Edition, CSA C22.2 No. 107.3-14 Third Edition
  • EMC IEC/EN 62040-2 C3
  • Manufacturing ISO 9001:2008

WEIGHT, DIMENSIONS

  • Weight (System With 6 Modules) 1517 Lbs. (688 Kg)
  • Dimensions WxHxD 31.16″ X 77.76″ X 35.17″ (791 X 893 X 1975.5 Mm)